• IT60-400

    Made for high accuracy. DC, AC pulse currents' measurements from 60 to 400 ADC nominal with galvanic isolation. Excellent linearity, better than 3 ppm. High resolution. Initial offset between 40 to 250 ppm. Very low offset drift: between 1 to 2.5 ppm/K. Overall accuracy @ Ipn?@ +25°C: between < +/- 0.0051% and < +/- 0.0285%. ,Wide frequency bandwidth up to 800 kHz (+/- 3 dB). Fluxgate technology. Electrostatic shield between primary and secondary circuit. Power supply +/-15 V. Operating temperature range from +10 to +50°C. D-Sub 9 male interface output. Current output. Really quick response time (<250 μs)

    Model details

    IT 60-S ULTRASTAB

    High accurate current transducer for 60 ARMS nominal.

    Series
    IT60-400
    Measurement
    Current
    Nominal Value
    60 A
    Measuring Range
    60 A
    Second. Nominal Signal
    Current
    Second. Nominal Signal Value
    Instantaneous 100 mA
    Primary Signal
    AC + DC
    Supply Voltage
    External DC Bipolar
    Supply Voltage Range
    15 - 15 V
    Accuracy
    0.02725 %
    Op. Temperature
    10 °C / 50 °C
    Technology
    Closed loop Fluxgate IT type
    Mounting
    Panel
    Applications
    High Precision
    PICTURE
    FRONT
    BACK
    LEFT
    RIGHT
    Order

    Contact Information

    Series

    Product of the same series