• IT700-1K

    Made for high accuracy. DC, AC pulse currents' measurements from 700 to 1000 ADC nominal with galvanic isolation. Excellent linearity, better than 3 ppm. High resolution. Initial offset between 50 to 60 ppm. Very low offset drift: between 0.5 to 4 ppm/K. Overall accuracy @ Ipn?@ +25°C: between < +/- 0.0059% and < +/- 0.015%. ,Wide frequency bandwidth up to 500 kHz (+/- 3 dB). Fluxgate technology. Electrostatic shield between primary and secondary circuit. Power supply +/-15 V. Operating temperature range from +10 to +50°C. D-Sub 9 male interface output. Current output. Really quick response time (<250 μs)

    Model details

    IT 700-SB ULTRASTAB

    High accurate current transducer for 700 ARMS nominal. +/- 10 V output. Linearity error 30 ppm. Sensitivity error 50 ppm.

    Series
    IT700-1K
    Measurement
    Current
    Nominal Value
    700 A
    Measuring Range
    700 A
    Second. Nominal Signal
    Voltage
    Second. Nominal Signal Value
    Instantaneous 10 V
    Primary Signal
    AC + DC
    Supply Voltage
    External DC Bipolar
    Supply Voltage Range
    15 - 15 V
    Accuracy
    0.0141 %
    Op. Temperature
    10 °C / 50 °C
    Technology
    Closed loop Fluxgate IT type
    Mounting
    Panel
    Applications
    High Precision
    IT 700-SB ULTRASTAB
    PICTURE
    FRONT
    BACK
    LEFT
    RIGHT