• DK Series

    Split Core (B series) and Solid Core (C series) DC current sensors for automation applications.

    DK – Automation current sensors

    The DK Series comprises split-core and solid-core current sensors engineered to accommodate AC current ranges from 5A to 200A, selectable by a jumper. Within this series, the DK-B Series (Split Core) allows for current measurements ranging from 50A to 200A, while the DK-C Series (Solid Core) covers a range from 5A to 100A.

    These sensors offer multiple output options, such as 4-20mA, 0-5V, or 0-10V, which can be selected via a jumper. The distinction between DK-B and DK-C lies in their core type, with "B" indicating split core and "C" indicating solid core.

    Additionally, the DK Series benefit from unique designations:

    • DK-5 and DK-10 denote sensors with voltage output capability (0-5V and 0-10V, respectively).
    • DK-420 signifies sensors with current output capability (4-20mA).

    Furthermore, the electronic parts carry additional specifications:

    • DK XXX B denotes sensors designed for bipolar DC current range measurement.
    • DK XXX U denotes sensors tailored for unipolar DC current range measurement.

    Utilizing open-loop hall effect technology, both the DK split-core and solid-core sensors are primarily suited for applications in the automation sector, but also in power supplies and renewables areas, where precise current measurement is critical.

    DK – Features and benefits

    DK automation current sensors

    Main characteristics

    • DC (magnitude only), DC bipolar (magnitude and direction) or DC unidirectional measurement
    • Split-core type (DK-B) or Solid-core (DK-C)
    • Three jumper selectable ranges
    • 0-5 V DC and 0-10 V DC jumper selectable voltage output or 4-20 mA current output
    • Panel mounting
    • From 1 % accuracy (Split Core) to 2 % (Solid Core)
    • Bandwidth DC
    • Insulating plastic case recognized according to UL 94-V0

    Benefits

    • Large aperture
    • Extended measuring range
    • High insulation between primary and secondary circuits
    • Easy to mount, cut installation costs
    • Power supply: +24 VDC
    • Isolation test voltage: 3 kVRMS / 50 HZ / 1 min
    • No insertion loss (voltage drop)

    Typical applications

    In the field of renewable energy, power supplies and automation, DK current sensors find application across various sectors. Some notable examples include:

    • Battery banks: Load current monitoring, Charging current monitoring, Operation supervision
    • Power supplies: DC power or auxiliary loads measurements
    • Electric heating elements: Faster response than temperature sensors

    LEM DK – Download & Technical Characteristic

    Product

    Order

    Document

    Primary nominal
     RMS voltage

    Output Type

    Secondary Nominal 
    Signal Value

    Op. Temperature

    DK 20 C10 U

    Datasheet5 A, 10 A, 20 AVoltage0-10V-20 to 50 °C
    DK 20 C420 B

     

    Datasheet5 A, 10 A, 20 ACurrent4-20mA-20 to 50 °C
    DK 20 C420 U

     

    Datasheet5 A, 10 A, 20 ACurrent4-20mA-20 to 50 °C
    DK 20 C5 U

    Datasheet5 A, 10 A, 20 AVoltage0-5V-20 to 50 °C
    DK 100 B10

    Datasheet50 A, 75 A, 100 AVoltage0-10V-20 to 50 °C
    DK 100 B420

    Datasheet50 A, 75 A, 100 ACurrent4-20mA-20 to 50 °C
    DK 100 B420 U

     

    Datasheet50 A, 75 A, 100 ACurrent4-20mA-20 to 50 °C
    DK 100 B5

     

    Datasheet50 A, 75 A, 100 AVoltage0-5V-20 to 50 °C
    DK 100 C10 U

    Datasheet50 A, 75 A, 100 AVoltage0-10V-20 to 50 °C
    DK 100 C420 B

     

    Datasheet50 A, 75 A, 100 ACurrent4-20mA-20 to 50 °C
    DK 100 C420 U

     

    Datasheet50 A, 75 A, 100 ACurrent4-20mA-20 to 50 °C
    DK 100 C5 U

     

    Datasheet50 A, 75 A, 100 AVoltage0-5V-20 to 50 °C
    DK 200 B10

    Datasheet100 A, 150 A, 200 AVoltage0-10V-20 to 50 °C
    DK 200 B420

    Datasheet100 A, 150 A, 200 ACurrent4-20mA-20 to 50 °C
    DK 200 B420 B

    Datasheet100 A, 150 A, 200 ACurrent4-20mA-20 to 50 °C
    DK 200 B420 U

    Datasheet100 A, 150 A, 200 ACurrent4-20mA-20 to 50 °C
    DK 400 B420

    Datasheet200 A, 300 A, 400 ACurrent4-20mA-20 to 50 °C

    DK Sensors – ASK FOR SAMPLES / QUOTATIONS

    Looking to receive samples or a quotation? Please click on the contact button below and provide us with the information you need on this product series. Our sales team will get back to you shortly.

    Contact Us